Output: Voltage and Current Ranges | |
Model |
CW 801M |
CW 1251M |
CW 2501M |
CW 801P |
CW 1251P |
CW 2501P |
Power |
800VA |
1250VA |
2500VA |
800VA |
1250VA |
2500VA |
Voltage |
Voltage Range |
0 to 135Vrms, 0 to 270Vrms, user selectable |
Accuracy (>5VAC) |
±1% of Range |
±0.1% of Range <100Hz ±0.2% of Range > 100Hz |
Resolution |
0.1 Vrms |
Total harmonic distortion |
0.25% typical <100Hz add 0.5%/100Hz above 100Hz |
AC noise level (typical) |
<50 mVRMS |
<50 mVRMS |
<100 mVRMS |
<50 mVRMS |
<50 mVRMS |
<100 mVRMS |
Amplitude stability1 |
±0.1% of full scale |
±0.05% of full scale |
Load regulation |
±0.1% of full scale voltage for a full resistive load to no load (<10 mVRMS typical, measured at point of sense) |
Line regulation |
±0.1% of full scale voltage for a ±10% line change from nominal line voltage (<5 mVRMS typical, measured at point of sense) |
Remote voltage sense |
5 Vrms total lead voltage drop |
Current |
135VAC Range |
6.0 ARMS |
9.4 ARMS |
18.6 ARMS |
6.0 ARMS |
9.4 ARMS |
18.6 ARMS |
270VAC Range |
3.0 ARMS |
4.7 ARMS |
9.3 ARMS |
3.0 ARMS |
4.7 ARMS |
9.3 ARMS |
Accuracy |
± 0.5% typical |
± 0.5% max |
Resolution |
0.1 ARMS |
0.01 ARMS |
Frequency Range |
Range |
45 to 500 Hz |
45 to 500 Hz, 45 to 1000 Hz (option) |
Accuracy |
±0.5% typical |
±0.02% max |
Resolution |
0.1 Hz |
0.1 Hz, 0.01 Hz for remote programming |
Phase |
All models single phase output. Multi-phase system configuration with Digital Expansion Cable |
Power Factor of Load |
0 lag to 0 lead | |
| |
|
|
Model |
CW 801M |
CW 1251M |
CW 2501M |
CW 801P |
CW 1251P |
CW 2501P |
Power |
800VA |
1250VA |
2500VA |
800VA |
1250VA |
2500VA |
Voltage |
Range |
0 to 270 Vrms |
0 to 270 Vrms, 0 to 310VRMS (option) |
Accuracy2 (VAC>5V) |
± 1% of full range |
±0.1% of range <100 Hz, ± 0.2% of range>100 Hz, ± 0.3% of range>500 Hz (option) |
Resolution |
0.1 Vrms |
0.1 Vrms |
Current3 |
135VAC Range |
6.0 ARMS |
9.4 ARMS |
18.6 ARMS |
6.0 ARMS |
9.4 ARMS |
18.6 ARMS |
Accuracy |
±2% of range for linear loads with current >0.2A, > 0.4A for 2500 VA |
±0.5% of range for linear loads |
Resolution |
0.1 ARMS |
0.01 ARMS |
Peak Current3 |
Range |
- |
- |
- |
0 to 25A |
0 to 35A |
0 to 70A |
Accuracy |
- |
- |
- |
±1% of Range |
Resolution |
- |
- |
- |
0.1A |
Frequency |
Range |
45 to 500 Hz |
45 to 500 Hz, 45-1 000 Hz (option) |
Accurace |
± 0.5% of reading |
± 0.02% of value |
Resolution of display |
0.1 Hz |
0.1 Hz | |
| |
|
|
Model |
CW 801P |
CW 1251P |
CW 2501P |
Power |
800 VA |
1250 VA |
2500 VA |
Power3 |
Range |
0 to 800W |
0 to 1250W |
0 to 2500W |
Accuracy |
±2% of range for linear loads |
Resolution |
1W |
Apparent Power3 |
Range |
0 to 800 VA |
0 to 1250 VA |
0 to 2500 VA |
Accuracy |
±2% of range for linear loads |
Resolution |
1 VA |
Power Factor3 |
Range |
0 to 1 |
Accuracy |
±4% of range for linear loads |
Resolution |
0.01 |
Crest Factor |
Range |
0 to 3.5 |
Accuracy |
±5% of range |
Resolution |
0.01 |
Phase |
Range |
-359 to +359 degrees. Positive indicates time lag from reference |
Accuracy |
Within 100 microseconds of equivalent angle |
Resolution |
1 degree | |
| |
|
|
Model |
CW 801M |
CW 1251M |
CW 2501M |
CW 801P |
CW 1251P |
CW 2501P |
Power |
800VA |
1250VA |
2500VA |
800VA |
1250VA |
2500VA |
Voltage |
90 to 264 VAC |
103 to 264 VAC |
180 to 264 VAC |
90 to 264 VAC |
103 to 264 VAC |
180 to 264 VAC |
Current |
13 ARMS max |
18.5 ARMS max |
19.5 ARMS max |
13 ARMS max |
18.5 ARMS max |
19.5 ARMS max |
Frequency |
47 to 63 Hz |
Phases |
single-phase |
Power Factor |
>0.99 typical at full load nominal line |
Efficiency |
>73% typical at full load | |
| |
|
|
Model |
CW 801M |
CW 1251M |
CW 2501M |
CW 801P |
CW 1251P |
CW 2501P |
Dimensions |
19 W x 5.216 H x 20.07 D |
19 W x 5.216 H x 20.07 D |
19 W x 5.216 H x 20.07 D |
19 W x 5.216 H x 20.07 D |
19 W x 5.216 H x 20.07 D |
19 W x 5.216 H x 20.07 D |
Weight |
48Lbs (22kg) |
53Lbs (24kg) |
86Lbs (39kg) |
48Lbs (22kg) |
53Lbs (24kg) |
86Lbs (39kg) |
Shipping Weight |
56Lbs (25kg) |
61Lbs (28kg) |
94Lbs (43kg) |
56Lbs (25kg) |
61Lbs (28kg) |
94Lbs (43kg) | |
| |
|
|
Front Panel Indicators |
Displays & indicators menu/status Enter/escape buttons are present for programming Voltage mode (volts, watts, VA, PF) Green LED Measure (amps, Hz, Pk amps, CF) Green LED Program (amps, Hz I Limit) Green LED Voltage range high/low Green LED |
Regulatory compliance |
CE mark, UL and CUL (consult factory for availability) | |
| |
|
|
Cooling |
Dual fan speed with side air intake, exhaust to rear
|
Operating temperature |
0 to 40°C
|
Storage temperature |
-40 to +70°C
|
Humidity |
0 to 85% at 25°C derate to 50% at 40°C (non condensing)
|
Altitude |
Operating full power available up to 6,000 feet, non operating to 40,000 feet | | | |
|
|
|
|
|
|
|