Specifications | Accuracy | Parameter | Range | Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) | Voltage | 1000 V | 0.1 V | ± (0.2 % + 0.01 %) | Current: Direct input | iFlex1500-12 | 150 A | 0.1 A | ± (1 % + 0.02 %) | 1500 A | 1 A | iFlex3000-24 | 300 A | 1 A | ± (1 % + 0.02 %) | 3000 A | 10 A | iFlex6000-36 | 600 A | 1 A | ± (1.5 % + 0.03 %) | 6000 A | 10 A | i40s-EL clamp | 4 A | 1 mA | ± (0.7 % + 0.02 %) | 40 A | 10 mA | Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ± (0.1 %) | Auxillary input | ± 10 V dc | 0.1 mV | ± (0.2 % + 0.02 %) | Voltage min/max | 1000 V | 0.1 V | ± (1 % + 0.1 %) | Current min/max | Defined by accessory | Defined by accessory | ± (5 % + 0.2 %) | Cosφ/DPF | 0 <= Cosφ <=1 | 0.01 | ± 0.025 | Power factor | 0 <= PF <=1 | 0.01 | ± 0.025 | THD on voltage | 1000 % | 0.1 % | ± (2.5 % ± 0.05) | THD on current | 1000 % | 0.1 % | ± (2.5 % ± 0.05) |
Intrinsic Uncertainty ± (% of reading + % of range)1 | Parameter | Influence quantity | iFlex1500-12 | iFlex3000-24 | iFlex6000-36 | i40S-EL | 150A/1500A | 300A/3000A | 600/6000A | 4A/40A | Active power P | PF ≥ 0.99 | 1.2 % + 0.005 % | 1.2 % + 0.0075 % | 1.7 % + 0.0075 % | 1.2 % + 0.005 % | 0.5 < PF < 0.99 | 1.2 % + 7 x (1-PF) +0.005 % | 1.2 % + 7 x (1-PF) + 0.0075 % | 1.7 % + 7 x (1-PF) + 0.0075 % | 1.2 % + 10 x (1-PF) + 0.005 % | Apparent power S, S fund. | 0 ≤ PF ≤ 1 | 1.2 % + 0.005 % | 1.2 % + 0.0075 % | 1.7 % + 0.0075 % | 1.2 % + 0.005% | Reactive power N, Q fund. | 0 ≤ PF ≤ 1 | 2.5 % of measured apparent power | Additional uncertainty in % of range1 | U >250 V | 0.015 % | 0.0225 % | 0.0225 % | 0.015 % | 1Range = 1000 V x Irange Reference conditions: Environmental: 23 °C ± 5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 % Input conditions: Cosφ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 % Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10 % of Irange Primary conductor of clamps or Rogowski coil in center position Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C |
Electrical Specifications | Power Supply | Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit | 100 V to 240 V using standard power cord (IEC 60320 C7) | Power consumption | Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) | Efficiency | ≥ 68.2 % (in accordance with energy efficiency regulations) | Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input | Mains power frequency | 50/60 Hz ± 15 % | Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable | On-battery runtime | Four hours in standard operating mode, up to 5.5 hours in power saving mode | Charging time | < 6 hours | Data Acquisition | Resolution | 16-bit synchronous sampling | Sampling frequency | 5120 Hz | Input signal frequency | 50/60 Hz (42.5 to 69 Hz) | Circuit types | 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies) | THD | THD for voltage and current is calculated using 25 harmonics | Averaging period | User selectable | 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min | Demand interval | User selectable | 5 min, 10 min, 15 min, 20 min, 30 min | Data storage | Internal flash memory (not user replaceable) | Memory size | Typical 20 logging sessions of 10 weeks with 10-minute intervals¹ | Logging period | Averaging period Recommended | 20 sessions | 1 session | 1 second | 3 hours | 2.5 days | 5 seconds | 15 hours | 12 days | 10 seconds | 28 hours | 24 days | 30 seconds | 3.5 days | 10 weeks | 1 minute | 7 days | 20 weeks | 5 minutes | 5 weeks | 2 years | 10 minutes | 10 weeks | > 2 years | 15 minutes | 3.5 months | > 2 years | 30 minutes | 7 months | > 2 years¹ | Interfaces | USB-A | File transfer via USB flash drive, firmware updates Max. current: 120 mA | USB-mini | Data download device to PC | Extension port | Accessories | Voltage Inputs | Number of inputs | 4 (3 phases and neutral) | Maximum input voltage | 1000 Vrms, CF 1.7 | Input impedance | 10 MΩ | Bandwidth (-3 dB) | 2.5 kHz | Scaling | 1:1, 10:1, 100:1, 1000:1 and variable | Measurement category | 1000 V CAT III/600 V CAT IV | Current Inputs | Number of inputs | 3, mode selected automatically for attached sensor | Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 | Rogowski coil input | 150 mVrms / 15 mVrms at 50 Hz, 180 mVrms / 18 mVrms at 60 Hz; CF 4; all at nominal probe range | Range | 1 A to 150 A/10 A to 1500 A with thin iFlex flexible current probe, 12 inches | 3 A to 300 A/30 A to 3000 A with thin iFlex flexible current probe, 24 inches | 6 A to 600 A/60 A to 6000 A with thin iFlex flexible current probe, 36 inches | 40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | Bandwidth (-3 dB) | 1.5 kHz | Scaling | 1:1 and variable | Auxiliary Inputs | Number of inputs | 2 | Input range | 0 to ± 10 V dc, 1reading/s | Scale factor (available 2014) | Format: kx + d user configurable | Displayed units (available 2014) | User configurable (7 characters, for example, °C, psi, or m/s) | - The number of possible logging sessions and logging period depends on user requirements.
|
Environmental Specifications | Operating temperature | -10 °C to +50 °C (14 °F to 122 °F) | Storage temperature | -20 °C to +60 °C (−4 °F to 140 °F) | Operating humidity | 10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH | 30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH | 40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH | Operating altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) | Storage altitude | 12,000m | Enclosure | IP50 in accordance with EN60529 | Vibration | MIL 28800E, Type 3, Class III, Style B | Safety | IEC 61010-1: Overvoltage CAT IV, Measurement 1000 V CAT III / 600 V CAT IV, Pollution Degree 2 | EMI, RFI, EMC | EN 61326-1: Industrial | Electromagnetic compatibility | Applies to use in Korea only. Class A equipment (industrial broadcasting and communication equipment) | Radio frequency emissions | IEC CISPR 11: Group 1, Class A | Temperature coefficient | 0.1 x accuracy specification/°C |
General Specifications | Color LCD display | 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel | Warranty | 1730 and power supply | Two-years (battery not included) | Accessories | One-year | Calibration cycle | Two-years | Dimensions | 1730 | 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in) | Power supply | 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in) | 1730 with power supply attached | 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in) | Weight | 1730 | 1.1 kg (2.5 lb) | Power supply | 400 g (0.9 lb) | External protection | Holster, Kensington lock slot |
1500-12 iFlex Flexible Current Probe Specifications | Measuring range | 1 to 150 A ac / 10 to 1500 A ac | Nondestructive current | 100 kA (50/60 Hz) | Intrinsic error at reference condition* | ± 0.7 % of reading | Accuracy 1730 + iFlex | ± (1 % of reading + 0.02 % of range) | Temperature coefficient over operating temperature range | 0.05 % of reading/°C 0.09 % of reading/°F | Working voltage | 1000 V CAT III, 600 V CAT IV | Probe cable length | 305 mm (12 in) | Probe cable diameter | 7.5 mm (0.3 in) | Minimum bending radius | 38 mm (1.5 in) | Output cable length | 2 m (6.6 ft) | Weight | 115 g | Transducer cable material | TPR | Coupling material | POM + ABS/PC | Output cable | TPR/PVC | Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176°F) | Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) | Relative humidity, operating | 15 % to 85 % non-condensing | IP rating | IEC 60529:IP50 | Warranty | One-year | *Reference condition:- Environmental: 23 °C ± 5 °C, no external electrical/magnetic field, RH 65 %
- Primary conductor in center position
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Features
Easily Discover Opportunities for Energy Savings for Your Facility The Fluke 1730 Three-Phase Electrical Energy Logger introduces a new simplicity to discovering sources of electrical energy waste. No other energy logger on the market can deliver a 600 V CAT IV/1000 V CAT III safety rating, directly download data from the instrument to a USB stick or store more logging sessions. With the 1730, you can: - Easily discover when and where energy is being consumed in your facility, from the service entrance to the individual circuits.
- Compare multiple data points over time and build the complete picture of energy usage with Fluke Energy Analyze software package.
- Quickly understand specific points of energy loss, reduce energy bills more easily than ever.
The Fluke 1730 is the best choice when looking for a dedicated energy logger for performing energy surveys and load studies. Take Energy Surveys to the Next Level If you’re looking to take your energy surveys to the next level, show up with the 1730 Energy Logger and a VT02 Visual IR Thermometer or the Ti125 Infrared Camera to quickly identify opportunities for energy savings both electrically and thermally. When using a thermal imaging camera or a visual IR thermometer along with the 1730 Energy Logger, you’ll be able to discover potential problems that could be wasting energy and then quantify them electrically with the 1730 Energy Logger. The perfect tool set to discover hidden operational wastes such as lighting, air conditioning and other large loads that could be switched off when not in use. - Key measurements: Voltage, current, power, power factor and associated values enable you to optimize and implement your energy saving strategies.
- Bright, color touch screen: Perform convenient in-the-field analysis and data checks with full graphical display.
- Comprehensive logging: More than 20 separate logging sessions can be stored on the instrument. In fact, all measured values are automatically logged and can be reviewed during logging and before downloading for on-the-go analysis.
- Optimized user interface: Capture the right data every time with quick, guided, graphical setup and reduce uncertainty about your connections with the intelligent verification function.
- Complete "in-the-field" setup through the front panel: no need to return to the workshop for download and setup or to take a computer to the electrical panel.
- Wide range power: power the instrument directly from the measured circuit eliminating the need to find a power outlet while allowing the instrument to be secured safely inside electrical panels.
- Two USB ports: one for PC connection and another for fast, simple download to standard USB thumb drives, or other USB devices.
- Compact size: designed to fit in tight spaces and panels.
- Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream.
- Optimized measurement accessories: flat voltage cable and thin flexible current probes ensure easy installation even in tight spaces.
- Battery life: four-hour operating time (backup time) per charge on lithium-ion battery.
- Security: We safeguard your best asset from theft with an option to use a hefty, durable Kensington lock.
- Energy Analyze application software: Download and analyze a snapshot of your energy savings potential with our automated reporting.
|
|
|
|
|
|
|